1、安(an)裝電氣火(huo)災監控系(xi)統的必要性

近幾(ji)年來,全(quan)國電(dian)(dian)(dian)氣火(huo)(huo)災事故(gu)(gu)數(shu)(shu)量呈上升(sheng)趨勢。引發電(dian)(dian)(dian)氣火(huo)(huo)災的(de)原因有很(hen)(hen)多,如:短(duan)路(lu)、過載、接地故(gu)(gu)障(zhang)、接觸電(dian)(dian)(dian)阻過大(da)、泄漏電(dian)(dian)(dian)流(liu)等。其(qi)中,接地故(gu)(gu)障(zhang)引起的(de)火(huo)(huo)災更(geng)具危(wei)險性。配(pei)電(dian)(dian)(dian)系統一般的(de)短(duan)路(lu)、過負荷容易被熔斷(duan)器、低壓(ya)斷(duan)路(lu)器等迅(xun)速切斷(duan)而不致(zhi)引起火(huo)(huo)災。接地故(gu)(gu)障(zhang)電(dian)(dian)(dian)流(liu)一般比較小,不足以(yi)(yi)使(shi)一般的(de)過電(dian)(dian)(dian)流(liu)保護及時切斷(duan)故(gu)(gu)障(zhang)。故(gu)(gu)障(zhang)點(dian)多數(shu)(shu)以(yi)(yi)電(dian)(dian)(dian)弧短(duan)路(lu)的(de)形式出現(xian)。由于(yu)電(dian)(dian)(dian)弧阻抗較大(da),它(ta)進一步限制(zhi)了故(gu)(gu)障(zhang)電(dian)(dian)(dian)流(liu),使(shi)過電(dian)(dian)(dian)流(liu)保護更(geng)難以(yi)(yi)動作,但其(qi)局部(bu)溫(wen)度卻(que)很(hen)(hen)高,2A的(de)電(dian)(dian)(dian)弧溫(wen)度可超過2 000℃ ,0.5A的(de)電(dian)(dian)(dian)弧能量已足以(yi)(yi)引燃(ran)可燃(ran)物質。所以(yi)(yi),防(fang)范 電(dian)(dian)(dian)氣短(duan)路(lu)火(huo)(huo)災的(de)重點(dian)是(shi)防(fang)范接地電(dian)(dian)(dian)弧短(duan)路(lu)。為了遏制(zhi)電(dian)(dian)(dian)氣火(huo)(huo)災的(de)上升(sheng)勢頭,政府等相(xiang)(xiang)關(guan)部(bu)門相(xiang)(xiang)繼制(zhi)訂或修改了有關(guan)標準(zhun)規范,要求在建筑中設置電(dian)(dian)(dian)氣火(huo)(huo)災監控系統。

2、電氣火災(zai)監(jian)控(kong)系統的功能

大多(duo)數的電(dian)氣(qi)火災監(jian)控設(she)備都(dou)具備以下的功能: 

1. 漏電預警和報警 

當配電(dian)(dian)回路的(de)漏(lou)電(dian)(dian)電(dian)(dian)流(liu)(liu)值(zhi)達到漏(lou)電(dian)(dian)報(bao)警(jing)(jing)或(huo)預警(jing)(jing)整定值(zhi)的(de) 80%~100%時,探(tan)測(ce)器發出漏(lou)電(dian)(dian)預警(jing)(jing)或(huo)報(bao)警(jing)(jing)信號(hao)。通過二總線主動上傳(chuan)給(gei)監控設備(bei),同時上傳(chuan)的(de)還有(you)報(bao)警(jing)(jing)線路地址、報(bao)警(jing)(jing)時現(xian)場電(dian)(dian)流(liu)(liu)及漏(lou)電(dian)(dian)值(zhi)、報(bao)警(jing)(jing)發生時間。 

2. 過電流預警和報警 

當配電回路的(de)過電流值(zhi)達到過電流預警或(huo)整(zheng)定值(zhi)的(de) 80%~100%時(shi),探測器發(fa)出過電流預警或(huo)報(bao)警信號。通過二(er)總線主動(dong)上傳(chuan)給監控設(she)備(bei),同時(shi)上傳(chuan)的(de)還有報(bao)警線路地址、報(bao)警時(shi)現場電流及(ji)報(bao)警發(fa)生(sheng)時(shi)間。 

3. 溫(wen)度報警 

監視**部(bu)位的溫度(du)(du)變化,并將溫度(du)(du)值實時(shi)(shi)傳(chuan)送給集中監控設(she)(she)備。當監視部(bu)位的溫度(du)(du)達到報警(jing)設(she)(she)定值時(shi)(shi),發(fa)出聲、光(guang)報警(jing)信號。 

4. 實時監控功能 

在電氣(qi)火災監(jian)控設備(bei)、微型計算機上,能夠顯示**點的三相工作電流(liu)(liu)和(he)漏電電流(liu)(liu)值,并能夠(gou)采用時間歷程曲線的方式顯示出這些(xie)電流(liu)(liu)值的大小和(he)變(bian)化趨勢。除了以上功(gong)能以外,還有隱(yin)患預(yu)警功(gong)能、顯示和(he)存(cun)儲等(deng)。 

3、電氣火災監控(kong)系(xi)統的設計(ji)依據 

GB 14287.1-2005《漏電(dian)火(huo)(huo)災監(jian)(jian)控(kong)設(she)(she)備》,GB14287.2-2005《剩(sheng)余電(dian)流式電(dian)器(qi)(qi)火(huo)(huo)災監(jian)(jian)控(kong)探測(ce)器(qi)(qi)》,GB14287.3-2005《測(ce)溫式漏電(dian)火(huo)(huo)災監(jian)(jian)控(kong)探測(ce)器(qi)(qi)》,GB 50016-2006《建筑(zhu)設(she)(she)計防火(huo)(huo)規(gui)范(fan)》,CB50045-95《高(gao)層民(min)用建筑(zhu)設(she)(she)計防火(huo)(huo)規(gui)范(fan)》2005 年局部修訂條文,GB50 016-2006《建筑(zhu)設(she)(she)計防火(huo)(huo)規(gui)范(fan)》,GB 13 955-2005《剩(sheng)余電(dian)流動作保護裝(zhuang)置(zhi)的(de)安(an)裝(zhuang)和運行》。  

4、電(dian)氣(qi)火災監控系統探測器的安裝(zhuang)方式(shi)

1. 配電箱或控制箱內部形式的(de)安(an)裝設計(ji) 

一(yi)般(ban)的(de)(de)工程中(zhong),在各樓層設有專門的(de)(de)層配電(dian)(dian)箱或控制箱,電(dian)(dian)氣火災(zai)監控探測(ce)器直接安裝在配電(dian)(dian)箱或控制箱內部適當位(wei)置。 

2. 配(pei)電箱(xiang)或控制(zhi)箱(xiang)(柜)外(wai)部形式的安裝設計 

電(dian)氣火災監控(kong)探(tan)測(ce)器(qi)(qi)單獨做成一個箱(xiang)(xiang)體(ti),將總電(dian)源通過電(dian)氣火災監控(kong)探(tan)測(ce)器(qi)(qi),再接(jie)入(ru)配(pei)電(dian)箱(xiang)(xiang)或控(kong)制(zhi)箱(xiang)(xiang)。對于新舊(改(gai)(gai)造)工程的(de)應用,電(dian)氣火災監控(kong)探(tan)測(ce)器(qi)(qi)只需將電(dian)源先引入(ru)漏(lou)電(dian)報(bao)警開關裝(zhuang)置后,再接(jie)入(ru)配(pei)電(dian)箱(xiang)(xiang)或控(kong)制(zhi)箱(xiang)(xiang)。專門(men)安裝(zhuang)漏(lou)電(dian)控(kong)制(zhi)器(qi)(qi)的(de)防火監控(kong)箱(xiang)(xiang)設(she)在配(pei)電(dian)箱(xiang)(xiang)或控(kong)制(zhi)箱(xiang)(xiang)附近。改(gai)(gai)造工程建議采(cai)用矩(ju)型的(de)漏(lou)電(dian)互感器(qi)(qi),可以盡量不觸動原來(lai)配(pei)電(dian)箱(xiang)(xiang)(柜)的(de)內(nei)部導線和器(qi)(qi)件布置。 

3. 配電柜成套形(xing)式(shi)的安裝(zhuang)設計(ji) 

直接在(zai)(zai)(zai)配電(dian)(dian)箱(xiang)或控制箱(xiang)面(mian)板上嵌入漏(lou)電(dian)(dian)控制器(qi),只考(kao)慮在(zai)(zai)(zai)柜(ju)內適當位(wei)置(zhi)固定電(dian)(dian)流互感器(qi)(一般在(zai)(zai)(zai)主空(kong)開(kai)上端或下端)。不改動配電(dian)(dian)柜(ju)內部結構,不需(xu)增加單獨的(de)(de)漏(lou)電(dian)(dian)控制器(qi)安裝箱(xiang),既(ji)美觀又不占(zhan)空(kong)間。應在(zai)(zai)(zai)設計中明確提出要求,在(zai)(zai)(zai)施(shi)工圖會審完(wan)畢,由(you)配電(dian)(dian)柜(ju)成套(tao)廠考(kao)慮預(yu)留面(mian)板上嵌裝電(dian)(dian)氣火災(zai)探測器(qi)的(de)(de)開(kai)孔尺寸。 

5、安科瑞(rui)電氣火災監控(kong)系統

5.1概述(shu)

Acre1-6000電(dian)(dian)(dian)(dian)氣火災(zai)監控(kong)系(xi)統(tong),是根(gen)據(ju)國家現(xian)行(xing)(xing)規范標準由安科瑞電(dian)(dian)(dian)(dian)氣股份有限公司研(yan)發的(de)(de)全數字化獨(du)立運行(xing)(xing)的(de)(de)系(xi)統(tong),已通過(guo)(guo)國家消(xiao)(xiao)防電(dian)(dian)(dian)(dian)子(zi)產品質量監督檢(jian)驗(yan)中心(xin)的(de)(de)消(xiao)(xiao)防電(dian)(dian)(dian)(dian)子(zi)產品試驗(yan)認證(zheng),并且(qie)均(jun)通過(guo)(guo)嚴格的(de)(de)EMC電(dian)(dian)(dian)(dian)磁兼容試驗(yan),保(bao)證(zheng)了該(gai)系(xi)列產品在(zai)低壓配電(dian)(dian)(dian)(dian)系(xi)統(tong)中的(de)(de)安全正常運行(xing)(xing),現(xian)均(jun)已批量生(sheng)產并在(zai)全國得到(dao)廣泛地應用。該(gai)系(xi)統(tong)通過(guo)(guo)對剩余電(dian)(dian)(dian)(dian)流(liu)(liu)、過(guo)(guo)電(dian)(dian)(dian)(dian)流(liu)(liu)、過(guo)(guo)電(dian)(dian)(dian)(dian)壓、溫度和(he)故(gu)障電(dian)(dian)(dian)(dian)弧(hu)等(deng)信號的(de)(de)采集與監視,實現(xian)對電(dian)(dian)(dian)(dian)氣火災(zai)的(de)(de)早期預(yu)防和(he)報(bao)警(jing),當必(bi)要(yao)時還能聯動切除被檢(jian)測到(dao)剩余電(dian)(dian)(dian)(dian)流(liu)(liu)、溫度和(he)故(gu)障電(dian)(dian)(dian)(dian)弧(hu)等(deng)超標的(de)(de)配電(dian)(dian)(dian)(dian)回路;并根(gen)據(ju)用戶(hu)的(de)(de)需(xu)求,還可以滿(man)足與AcreIEMS企業微電(dian)(dian)(dian)(dian)網管理云(yun)平(ping)臺或火災(zai)自動報(bao)警(jing)系(xi)統(tong)等(deng)進行(xing)(xing)數據(ju)交換和(he)共(gong)享(xiang)。

5.2 應用場合

適用于智能樓宇、高層公寓、賓(bin)館、飯店、商(shang)廈、工礦企(qi)業、國家重(zhong)點消(xiao)防單位以及石油化工、文教衛生、金融、電信等領(ling)域(yu)。

5.3 系統結構

IMG_256 

5.4 系統功能

1) 監控設備(bei)(bei)能接收多臺(tai)探(tan)測器的剩余電(dian)流、溫度信(xin)息,報(bao)(bao)(bao)(bao)警(jing)(jing)(jing)時(shi)(shi)發出(chu)聲(sheng)、光(guang)報(bao)(bao)(bao)(bao)警(jing)(jing)(jing)信(xin)號(hao),同時(shi)(shi)設備(bei)(bei)上紅色“報(bao)(bao)(bao)(bao)警(jing)(jing)(jing)"指示(shi)燈(deng)亮,顯示(shi)屏指示(shi)報(bao)(bao)(bao)(bao)警(jing)(jing)(jing)部位(wei)及報(bao)(bao)(bao)(bao)警(jing)(jing)(jing)類型(xing),記錄(lu)報(bao)(bao)(bao)(bao)警(jing)(jing)(jing)時(shi)(shi)間,聲(sheng)光(guang)報(bao)(bao)(bao)(bao)警(jing)(jing)(jing)一直(zhi)保持,直(zhi)至按(an)(an)設備(bei)(bei)的“復位(wei)"按(an)(an)鈕或觸摸屏的“復位(wei)"按(an)(an)鍵遠程對探(tan)測器實(shi)現(xian)復位(wei)。對于(yu)聲(sheng)音報(bao)(bao)(bao)(bao)警(jing)(jing)(jing)信(xin)號(hao)也可以使用觸摸屏“消聲(sheng)"按(an)(an)鍵手動消除。

IMG_257 

2)當被(bei)(bei)監測回路報(bao)警時,控制輸出(chu)繼(ji)電器閉(bi)合,用(yong)于控制被(bei)(bei)保護電路或其他設(she)備,當報(bao)警消除后,控制輸出(chu)繼(ji)電器釋放(fang)。

3)通訊(xun)故(gu)障(zhang)(zhang)報(bao)警(jing)(jing):當監控設備與所接的(de)任一(yi)臺探(tan)測(ce)(ce)器之間發生(sheng)通訊(xun)故(gu)障(zhang)(zhang)或探(tan)測(ce)(ce)器本身(shen)發生(sheng)故(gu)障(zhang)(zhang)時,監控畫面中相應的(de)探(tan)測(ce)(ce)器顯示故(gu)障(zhang)(zhang)提示,同時設備上的(de)黃色“故(gu)障(zhang)(zhang)"指(zhi)示燈亮,并(bing)發出(chu)故(gu)障(zhang)(zhang)報(bao)警(jing)(jing)聲音。電(dian)源故(gu)障(zhang)(zhang)報(bao)警(jing)(jing):當主(zhu)電(dian)源或備用電(dian)源發生(sheng)故(gu)障(zhang)(zhang)時,監控設備也發出(chu)聲光報(bao)警(jing)(jing)信號(hao)并(bing)顯示故(gu)障(zhang)(zhang)信息,可進入相應的(de)界面查看詳(xiang)細(xi)信息并(bing)可解除報(bao)警(jing)(jing)聲響。

IMG_258 

4)當(dang)發生剩余電(dian)流、超(chao)溫報(bao)警或通訊、電(dian)源故(gu)障時,將報(bao)警部位、故(gu)障信息、報(bao)警時間等信息存儲在(zai)數(shu)據庫(ku)中,當(dang)報(bao)警解除、排除故(gu)障時,同樣予以記錄。歷史數(shu)據提(ti)供多種(zhong)便捷、快速(su)的查詢(xun)方(fang)法(fa)。

IMG_259 

5.5 配置方案

IMG_260 

IMG_261 

6、結(jie)束語

隨(sui)著(zhu)現代化社會(hui)的(de)快速發展,人(ren)們(men)的(de)用電量不 斷(duan)增加,整個社會(hui)對(dui)電氣火(huo)災(zai)監(jian)控系統也越來越重視。"把保障人(ren)民群眾的(de)生命安全和(he)(he)身體健康,預防(fang)和(he)(he)減少(shao)安全生產事故災(zai)難造成的(de)人(ren)員傷亡作(zuo)為首(shou)要任(ren)務(wu)"是我們(men)所有建筑(zhu)電氣人(ren)員的(de)共同目標(biao)和(he)(he)希(xi)望。以人(ren)為本(ben),安全第一。電氣火(huo)災(zai)監(jian)控系統也將隨(sui)著(zhu)建筑(zhu)設計(ji)防(fang)火(huo)規(gui)范相(xiang)關條款更加完善,得到更好地改進和(he)(he)應(ying)用。